Hi Robin,
maybe you want to try this. For this demo I created 3 signals based on the example data of Seeq as I did not have data like yours. For each of the signals I created capsules whenever the value is above 1kW:
In the next step I joined the running conditions to one parent condition:
Now I am able to calculate the delay between the start of the "All running" capsules and the "Running" capsules of each signal and delay the original signal by this value:
In the last step I created capsules for the delayed signal, whenever the value is about 1kW:
You may have to do some adjustments to this example regarding your needs. Hope this helps.
Regards,
Thorsten